PowerFlex 700S - Frame 10

No.

Name

Description

Wire Size Range

(1)(2)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

(2)

Do Not exceed maximum wire size. Parallel connections may be required.

Torque

Terminal Bolt
Size

(3)

(4)

(3)

These connections are bus bar type terminations and require the use of lug type connectors.

(4)

Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

Maximum

Minimum

Recommended

1

Input Power Terminal Block
L1, L2, L3

(3)

Input power

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N-m
(354 lb.-in.)

M12

2

Output Power Terminal Block

((3)

U/T1, V/T2, W/T3

Motor connections

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N-m
(354 lb.-in.)

M12

3

SHLD Terminal, PE, Motor Ground

(3)

Terminating point for wiring shields

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N-m
(354 lb.-in.)

M10

4

DC Bus

(3)

(2 Terminals; DC–, DC+)

DC input or external brake

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N-m
(354 lb.-in.)

M12

5

Cable Clamp for Shield

DANGER

DANGER

DC BUS CONDUCTORS AND CAPACITORS

OPERATE AT HIGH VOLTAGE. REMOVE POWER

AND WAIT 5 MINUTES BEFORE SERVICING

Cat No.

1234567890-*

1234567890-*

FIELD INSTALLED OPTIONS:

FIELD INSTALLED OPTIONS:

DC-

DC+

L1

L2

L3

U/T1

V/T2

W/T3

2

1

5

4

3