Calibration, Factory default settings – Rockwell Automation 150 SMC Dialog Plus Controller - Quick Start User Manual

Page 14

Advertising
background image

14

Rockwell Automation Publication 150-QS002B-EN-P - October 2011

Quick Start

Factory Default Settings

The SMC Dialog Plus controller is pre-programmed with the settings listed in
the table below.

Saving Programmed Values to Memory

After you have programmed the controller settings you

must save them to the

controller’s memory. To do this, follow the steps below:

1. Scroll to Parameter Mgmt. This is the last parameter provided in the Basic

Setup, Advanced Setup, and Calibrate programming groups.

2. Select the Store In EE option.
3. Press Enter.

Calibration

For current measurement accuracy, use the procedure below to calibrate the SMC
Dialog Plus controller to the connected motor. A clamp-on ammeter, which
provides a true rms measurement and has a published accuracy of ±1% (Fluke
model 33 or equal), is required to perform this procedure.

Parameter

Setting

Starting Mode

Soft Start

Ramp Time

10 seconds

Initial Torque

70% of locked rotor torque

Kickstart

Off

Energy Saver

Off

Stall

Off

Phase Rebalance

Off

Auxiliary Contacts

Normal

Service Factor

1.15

Overload Class

Off

Line Voltage

480 volts

Motor FLC

1.0 amps

Motor HP Rating

0.0 HP

Motor Code Letter

G

ATTENTION: Overload protection in the SMC Dialog Plus controller is
disabled from the factory. The user must program the desired overload
trip class and motor full load current rating to achieve proper protection

IMPORTANT

If control power is removed from the SMC Dialog Plus controller before
you store the programmed values to memory, all programmed values will
be lost.