Rockwell Automation Publication 150-QS002B-EN-P - October 2011

17

Quick Start

Human Interface Modules

The Bulletin 1201 human interface modules with control panels can start and
stop the SMC Dialog Plus controller. However, the factory default settings
disable control commands other than Stop through the serial communication
port.

To enable motor control from a connected human interface module, you must
take the following programming steps:

Series A

1. Enter into the Program mode.
2. Select the Linear List programming group.
3. Scroll to the Logic Mask parameter (number 85).
4. Program the Logic Mask parameter for a value of 4.
5. Press Enter.

Series B

1. Enter the Control Status mode.
2. Select the Enable option of Control Logic.
3. Press Enter.

IMPORTANT

Control Logic must be disabled or the Logic Mask set to 0 prior to
disconnecting a human interface module from the SMC Dialog Plus
controller.