Wiring

Power Wiring

Refer to the product nameplate for power lug termination information
including:

• Lug wire capacity
• Tightening torque requirements
• Lug kit catalog numbers (97…1000 A)

Control Wiring

Refer to the product nameplate for control terminal wire capacity and tightening
torque requirements. Each control terminal will accept a maximum of two wires.

The SMC Dialog Plus controller accepts control power input of either
100…240V AC, (+10/–15%) single-phase, 50/60 Hz or 24V AC/DC. Refer to
the product nameplate prior to applying control power. Connect control power
to the controller at terminals 11 and 12. The control power requirement for the
control module is 40 VA. For controllers rated 97…1000 A, control power is also
required for the heatsink fans as defined in Table A. Depending on the specific
application, additional control circuit transformer VA capacity may be required.

Control Terminals

Figure 1 - SMC Dialog Plus Controller Control Terminals

Table 1 - Heatsink Fan Power Requirements

SMC Rating

Heatsink Fan VA

97…360 A

45

500 A

145

650…1000 A

320

Table 2 - Control Terminal Designation

Terminal Number

Description

11

Control Power Input

12

Control Power Common

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30