Rockwell Automation Publication 150-QS002B-EN-P - October 2011

15

Quick Start

Notes:

1. If you plan to use the Bulletin 825 converter module for current feedback

to the SMC Dialog Plus controller, this calibration procedure is not
necessary.

2. An unbalanced three-phase system may affect the accuracy of the

calibration.

3. It is recommended that Parameter #36, Overload Class, is programmed to

OFF during the calibration procedure.

Calibration requires the motor to be operated at full speed. Additionally, the
motor must be connected to its load in order that the motor draw as near to its
full load current (FLC) rating as possible. This is necessary so that maximum
accuracy is achieved for current measurements at overload trip levels.

➊The currents should measure a minimum of 70% of the motor’s full load current rating in order to achieve the best

results in accuracy.

Description

Action

Display

1. Check all power and control wiring connections to the

controller and motor. Apply a start command to the
controller and check for motor rotation to full speed.

_

2. Using the clamp-on ammeter, measure the three-phase

motor currents. Place the ammeter around the phase
with the largest current draw.

_

3. In the Calibrate group, scroll to the Calibration

parameter.

4. Monitor the clamp-on ammeter and verify that the motor

current is stable. Press the Select key. Toggle the
Up/Down keys to the Activate setting. Press the Enter
key to accept. Monitor the ammeter display for the next
2 seconds and record the average value. During this time
period, the SMC Dialog Plus controller samples motor
response data.

5. Access the next parameter using the Up key.

6. Press the Select key. Enter the clamp-on meter value

monitored in step 4. Press the Enter key to accept. The
SMC Dialog Plus controller is now calibrated.

AT SPEED
##.# AMPS

AT SPEED
##.# AMPS

CALIBRATION
OFF

SEL

CALIBRATION
ACTIVATE

ENTER CALIB. AMPS
0.0 AMPS

SEL

ENTER CALIB. AMPS
##.# AMPS