Quick Start

Communication

A serial interface port (called SCANport

™) is provided as standard, and allows

connection to a Bulletin 1201 human interface module or a variety of Bulletin
1203 communication modules.

Figure 6 - SCANport Location

Description

Action

Display

7. You can scroll to the next parameter to view the current

measurement in phase A.

8. Scroll to the next parameter to save the Calibrate group

settings.

9. Press the Select key. Scroll with the Up/Down keys to

Store In EE selection. Press the Enter key to save the
settings to EEPROM.

ATTENTION: After calibration is completed, program the desired
overload class and save the setting to the controller’s EEPROM.

ATTENTION: The method of current measurement is not applicable to
the multi-motor installations or resistive heating loads. Utilization of the
Bulletin 825 converter module is required for these applications if
current measurement is required.

CURRENT PHASE A
##.# AMPS

PARAMETER MGMT
READY

SEL

PARAMETER MGMT
STORE IN EE

ATTENTION: Only one peripheral device can be connected to the
SCANport. The maximum output current is 100 mA.

ESC.

SEL .

SCANport