SMC™ Flex Quick Start

Access the Basic set up group by selecting the Parameters menu from the Main Menu and then Set Up.This
programming group provides a limited parameter set, allowing quick start-up with minimal adjustment.

Parameter Name and Description

Values

Default

Parameter # 14 - SMC Option

Displays the type of controller. This is factory set and not adjustable.

Standard, Pump Control, Brake

Read Only

Parameter # 15 - Motor Connection

Displays the motor type to which the device is being connected.

Line or Delta

Line

Parameter # 16 - Line Voltage

Displays the system line voltage to which the unit is connected.

0…10000

480

Parameter # 17 - Starting Mode

Allows the user to program the SMC-Flex controller for the type of starting that best fits the application.

Soft Start, Current Limit, Full
Voltage, Linear Speed, Pump
Control

Soft Start

Parameter # 18 - Ramp Time

This sets the time period during which the controller will ramp the output voltage.

0…30 s

10

Parameter # 19 - Initial Torque

When the Soft Start mode is selected, this parameter sets the initial reduced voltage output level for the
voltage ramp.

0…90% of locked rotor torque

70

Parameter # 20 - Current Limit Level

When Current Limit mode is selected, this parameters sets level of current that is applied for the
programmed Ramp Time.

50…600% FLC

350

Parameter # 22 - Kickstart Time

A boost current is provided to the motor for the programmed time period.

0.0…2.0 s

0

Parameter # 23 - Kickstart Level

Adjusts the amount of current applied to the motor during kickstart.

0…90% of locked rotor torque

0

Parameter # 133 - Stop Input

Allows the user to select the operation of terminal 18, Stop Input.

Coast, Stop Option

Coast

Parameter # 132 - Option Input 1

Allows the user to select the operation of terminal 16, Option Input #1.

Disable, Coast, Stop Option,
Fault, Fault NC, Network

Stop Option

Parameter # 24 - Option Input 2

Allows the user to select the operation of terminal 15, Option Input #2.

Disable, Slow Speed, Dual Ramp,
Fault, Fault NC, Network, Clear
Fault

Disable

Parameter # 32 - Stop Mode

Allows the user to program the SMC Flex controller for the type of stopping that best fits the application.

Soft Stop, Linear Speed, SMB,
Accu-Stop, Pump Stop

Soft Stop

Parameter # 33 - Stop Time

This sets the time period which the controller will ramp the voltage during a stopping maneuver.

0.0…120 s

0.0

Parameter # 44 - Overload Class

Allows the user to enter the desired Overload trip class for the motor.

Disable, 10, 15, 20, 30

10

Parameter # 45 - Service Factor

Allows the user to enter the Service Factor of the motor. For IEC motors the typical value is 1.0. For NEMA

0.01…1.99

1.15

Parameter # 46 - Motor FLC

This is a user entered value that is needed so the device can provide proper motor Overload protection.

1.0…2200

1.0

Parameter # 47 - OL Reset Mode

This value allows the user to define how the overload can reset.

Auto, Manual

Manual

Parameter # 107 - Aux1 Config

Auxiliary 1 contact is located at terminals 19 and 20 and allows the user to configure the operation of the
contact.

Normal, Up-to-speed, Fault,
Alarm, Network Control, External
Bypass: (N.O./N.C.)

Normal

Parameter # 110 - Aux2 Config

Auxiliary 2 contact is located at terminals 29 and 30 and allows the user to configure the operation of the
contact.

Normal, Up-to-speed, Fault,
Alarm, Network Control, External
Bypass: (N.O./N.C.)

Fault

Parameter # 108 - Aux3 Config

Auxiliary 3 contact is located at terminals 31 and 32 and allows the user to configure the operation of the
contact.

Normal, Up-to-speed, Fault,
Alarm, Network Control, External
Bypass: (N.O./N.C.)

Alarm

Parameter # 109 - Aux4 Config

Auxiliary 4 contact is located at terminals 33 and 34 and allows the user to configure the operation of the
contact.

Normal, Up-to-speed, Fault,
Alarm, Network Control, External
Bypass: (N.O./N.C.)

Normal

Parameter # 115 - Parameter Mgmt

Allows the user the ability to recall all Factory default parameter values.

Ready, Load Default

Ready