Control wiring – Rockwell Automation 150 SMC Flex Quick Start User Manual

Page 7

Advertising
background image

SMC™ Flex Quick Start 7

Control Wiring

Refer to the product nameplate for additional details. Depending on the specific application, additional control
circuit transformer VA capacity may be required.

Controllers rated 5…480 A

Control power is connected to the product through terminals 11 and 12.

Controllers rated 625…1250 A

Control power is connected to the product through terminal block CP1, at terminals 1 and 4.

Conductor Range

0.75…2.5 mm

2

(18…14 AWG)

Torque

0.6 N•m (5 lb•in)

Maximum Number of Wires per Terminal

2

AC Control Voltage Input

100…240V AC or 24V AC (+10/-15%)

Supply Type

1-phase, 50/60 Hz

24V AC Power Requirement

130VA

100…240V AC Power Requirement

75VA

DC Control Voltage Input

24V DC (+10/-15%)

Inrush Current

5 A

Inrush Time

250 ms

Transient Watts

60 W

Transient Time

500 ms

Staedy State Watts

24 W

Recommended Supply

1606-XLP50E

Fan Power Input (AC only)

separately wired

F5…F135

20VA

F201…F251

40VA

F317…F480

60VA

Conductor Range

0.75…2.5 mm

2

(18…14 AWG)

Torque

0.6 N•m (5 lb•in)

Maximum Number of Wires per Terminal

2

Control Voltage Input

110/120V AC or 230/240V AC, (+10/-15%)

Supply Type

1-phase, 50/60 Hz

Control Power Input

800VA (includes controller, bypass, and fans)