SMC™ Flex Quick Start 13

Step 4 - Operation and Troubleshooting

Start Up Check List

1. Verify Input Supply voltage and wiring

2. Check output wiring

3. Check control wiring

4. Apply control power

5. Test local start/stop control

Monitoring

The SMC Flex controller has built in diagnostics and metering functions which can be accessed through a local or
remote LCD display.

Viewing and Clearing Faults

Step

Action

1

From any menu, Press Esc to get to the MAIN Device display.

2

If using the built in display, Press Enter and continue to step #3.

If using a remote HIM, first make sure that the SMC Flex is displayed by going to
MAIN MENU / DEVICE SELECT / SMC FLEX Press Enter and continue to step #3.

3

To View or Review the Metering Information

- Access the metering parameters by selecting PARAMETER / MONITORING / and then METERING. Press enter to view
any selected value.

Step

Action

1

Press Esc to acknowledge the fault. The fault information will be removed so that you can use the HIM.

2

To View or Review the fault information

- Go to MAIN MENU / DIAGNOSTICS / FAULTS / VIEW FAULT QUEUE.
- Or look at parameters 124…128.

3

Address the condition that caused the fault. The cause must be corrected before the fault can be cleared.

4

After corrective action has been taken, clear the fault by one of these methods:

- Press and Hold the ESC key for 3 seconds.
- Cycle control power to the device.
- Press Stop key on an External HIM.
- Program the SMC-Flex controller for a CLEAR FAULT, which can be found in MAIN MENU / DIAGNOSTICS / FAULTS.
- Option Input #2 (terminal 15) can be configured to clear faults with the use of N.O. push button.