Troubleshooting - abbreviated listing – Rockwell Automation 150 SMC Flex Quick Start User Manual

Page 14

Advertising
background image

14

SMC™ Flex Quick Start

Troubleshooting - Abbreviated Listing

For a complete list of fault codes and troubleshooting tips, refer to the SMC Flex User Manual.

Display Fault Fault Code

Enabled

Possible Causes

Possible Solutions

Line Fault with
Phase Indication

1, 2, 3

prestart

only

Missing supply phase

Motor not connected properly

Incoming 3-phase voltage instability

Check for open line (i.e., blown fuse)

Check for open load lead

Verify power quality

Shorted SCR
with Phase
indication

4, 5, 6

all

Shorted power module

Check for shorted SCR, replace power module if necessary

Open Gate with
Phase Indication

7, 8, 9

start or

stop

Open gate circuitry

Loose gate lead

Perform resistance check; replace power module if necessary

Check gate lead connections to the control module

PTC Power Pole
and SCR
Overtemp

10, 11

Controller ventilation blocked

Controller duty cycle exceeded

Fan failure

Ambient temperature limit exceeded

Failed thermistor

Check for proper ventilation

Check application duty cycle

Wait for motor to cool or provide external cooling

Replace power module or control module as needed
Replace fan

Motor PTC

12

running

Motor ventilation blocked

Motor duty cycle exceeded

PTC open or shorted

Check for proper ventilation

Check application duty cycle

Wait for motor to cool or provide external cooling

Check resistance of PTC

Open Bypass
with phase
indication

13, 14, 15

running

Control voltage is low

Inoperable power module bypass

Check control voltage power supply

Replace power module

Check control module TB2…TB4 and TB5…TB7 for securness

Check Aux 1, 2, 3, 4 configurations are not set to External
Bypass

No Load Fault

16, 17, 18, 40

prestart

only

Loss of load side power wiring

Start command cycled unexpectedly with motor rotating

Check all load side power connections

Check motor windings

Line Unbalance

19

running

Supply unbalance is greater than the user-programmed value

The delay time is too short for the application

Check power system and correct if necessary

Extend the delay time to match the application requirements

Overvoltage

20

running

Supply voltage is greater than user programmed value

The delay time is too short for the application

Check power system and correct if necessary

Correct the user-programmed value

Extend the delay time to match the application requirements

Undervoltage

21

running

Supply voltage is less than user programmed value

The delay time is too short for the application

Check power system and correct if necessary

Correct the user-programmed value

Extend the delay time to match the application requirements

Overload

22

running

Motor overloaded

Overload parameters are not matched to the motor

Check motor overload condition

Check values for overload class and motor FLC

Verify current draw of the motor

Underload

23

running

Broken motor shaft, belts, toolbits, etc..

Pump cavitation

Incorrect user setting

Check pump system, machine drive components, and loading

Check settings

Repair or replace motor

Jam

24

running

Motor current has exceeded the user programmed jam level

Correct source of jam or excessive loading

Check programmed time value

Stall

25

running

Motor did not reach full speed by the end of the programmed
ramp time

Incorrect user setting

Correct source of stall or excessive loading

Adjust SMC starting parameters to compensate for load

Phase Reversal

26

prestart

only

Incoming supply voltage is not in the expected ABC sequence

Check power wiring, correct if necessary

Network and
Comm's Loss

30, 31, 32
27, 28, 29

all

DPI network loss

Communication disconnection at the serial port

Check communication adapters and verify connection to SMC

Reconnect each DPI connected device

Ground Fault

33

running

Ground fault current level has exceeded programmed value

The delay time is too short for the application

Check power system and motor; correct if necessary

Check programmed ground fault levels to match application
requirements

Extend the delay time to match the application requirements

Power Loss with
phase indication

35, 36, 37

start or

stop

Missing supply phase (as indicated)
Internal CT problem

Check for open line (i.e., blown line fuse)
Replace power pole as indicated

Line Loss with
phase indication

41, 42, 43

start or

stop

Incoming 3-phase voltage instability or distortion

High impedance connection

Check supply voltage for capability to start/stop motor

Check for loose connections on line side or motor side of
power wires

Verify and correct input power quality

Internal 24V and
System Faults

44, 45, 46,

128…209

all

Low line condition

Excessive load on

Check the control power, verify it is within the specification

Check connections and grounding to the SMC control
terminals

Replace control module

Advertising