Rockwell Automation 1609-P10000E 8000 / 10000 VA Uninterruptible Power Supply User Manual

Page 10

Advertising
background image

9

N

OTE

:

S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE

,

OPTIONAL

N

ETWORK

M

ANAGEMENT CARDS

,

OR

T

ERMINAL

M

ODE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELEC TABLE

C

HOICES

D

ESCRIPTION

Low Bypass Point

-30% of output
voltage setting

-15%, -20%, -25%, -30%

Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.

Output Voltage

208/230 V models:
230 VAC

208/230 V models:
200, 208, 220,
230, 240 VAC

Allows the user to select the
UPS output voltage while
online.

Output Frequency

Automatic

50 ± 3 Hz or
60 ± 3 Hz

50 ± 3 Hz
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 0.1 Hz

Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.

Number of Battery
Packs

1

Number of Connected
Batteries (four battery
modules per pack)

Defines the number of
connected battery packs for
proper runtime prediction.

Advertising