Roubleshooting – Rockwell Automation 1609-P10000E 8000 / 10000 VA Uninterruptible Power Supply User Manual

Page 14

Advertising
background image

13

T

ROUBLESHOOTING

P

ROBLEM AND

P

OSSIBLE

C

AUSE

S

OLUTION

UPS

WILL NOT TURN ON

Batteries are not connected
properly.

Check that the battery connectors are fully engaged.

button not pushed.

Press the

button once to power the UPS and the connected equipment.

UPS not connected to utility
power supply.

Check that the power cable from the UPS to the utility power supply is securely
connected at both ends.

Very low or no utility voltage.

Check the utility power supply to ensure proper voltage at the receptacle.

UPS

WILL NOT TURN OFF

button not pushed.

Press the

button once to turn the UPS off.

Internal UPS fault.

Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.

UPS

BEEPS OCCASIONALLY

Normal UPS operation when
running on battery.

None. The UPS is protecting the connected equipment.

UPS

DOES NOT PROVIDE EXPECTED BACKUP TIME

The UPS battery module(s) are
weak due to a recent outage or
are near the end of service life.

Charge the battery module(s). Modules require recharging after extended outages
and wear faster when put into service often or when operated at elevated
temperatures. If the battery module(s) are near the end of service life, consider
replacing, even if the Replace Ba ttery LED is not illuminated.

FRONT PANEL

LED

S FLASH SEQUENTIALLY

The UPS has been shut down
remotely through software or an
optional accessory card.

None. The UPS will restart automatically when utility power returns.

ALL

LED

S ARE OFF AND THE

UPS

IS CONNECTED TO UTI LITY POWER

The UPS is shut down and the
battery is discharged from an
extended outage.

None. The UPS will return to normal operation when the power is restored and
the ba ttery has a sufficient charge.

BYPASS AND OVERLOAD

LED

S ILLUMINATE

,

UPS

EMITS A SUSTAINED ALARM TONE

The UPS is overloaded.

The connected equipment exceeds the specified “maximum load” as defined in
Specifications in the Quick Start Guide.

The alarm remains on until the overload is removed. Disconnect nonessential
equipment from the UPS to eliminate the overload condition.