Rockwell Automation Publication 1608P-UM003A-EN-P - September 2013

Chapter 6

Maintenance

Fuse Rating Charts

Replace fuse with the same type or equivalent cross-referenced rating. You may
order these fuses through Rockwell Automation or the manufacturer listed.

Table 11 - Pro DySC Fuse Ratings

Transient Voltage Surge
Suppressor (TVSS)

The ProDySC includes an internal TVSS device (or SPD), protecting the output
(load). Indicator lights on the TVSS show if surge protection is active. Power to
the TVSS module may be removed by opening the block of fuses F16-F17-F18-
F20. F20 is present only in 4-wire models.

Circuit Breaker CBI, Safety
Interlocks and Stored Energy

If the cabinet doors are opened while the ProDySC is operating the circuit
breaker CBI will be automatically opened and load power will be interrupted.
Doors should be kept locked to avoid this situation. CBI is rated 250A, 3-pole,
with thermal-magnetic trip and automatic shunt trip capability.

The ProDySC includes a fast-discharge circuit to quickly dissipate stored energy
when the internal circuit breaker CBI is opened. CBI may be operated
automatically by the door interlock switches or other protection devices. CBI
can also be operated manually. The recommended procedure for performing any
service inside the ProDySC begins with opening CBI before removing upstream
power.

If the upstream power is interrupted before CBI is opened the fast-discharge
circuit will not be triggered. In that case wait at least 30 minutes before opening
the ProDySC doors to avoid exposure to charged capacitors. High voltage

Fuse Reference

Fuse Location

Fuse Rating

Manufacturer

Part Number

F1, F2, F3

Main Cabinet: Main Power Input

600A/500V

Mersen A50QS600-4IL

F4, F5, F6

Main Cabinet: Cross-Coupling Transformer

100A/600V

Mersen AJT100

F7, F8, F9 (3 wire models only)

Main Cabinet: Neutral Forming Transformer

4A/600V

Mersen TRS4R

F10, F11 (200-220V models)

Main Cabinet: Input Control Transformer

2A/600V

Mersen TRS2R

F10, F11 (380-480V models)

Main Cabinet: Input Control Transformer

1A/600V

Mersen TRS1R

F12, F13

Main Cabinet: Cross Coupler Auxiliary

2A/600V

Mersen ATQR2

F14, F15 (200-220V models)

Main Cabinet: Output Control Transformer

8A/600V

Mersen TRS8R

F14, F15 (380-480V models)

Main Cabinet: Output Control Transformer

4A/600V

Mersen TRS4R

F16, F17, F18, F20

Main Cabinet: TVSS Input

40KA surge / 600V

Mersen VSP40-2

F19

Main Cabinet: Input Control Transformer

4A/600V

Bussmann FNQ-R-4

F1, F2

Power Module (x3): Voltage Feedback

2A/600V

Mersen ATQR2

F3

Power Module (x3):

--

Not Field Replaceable

F4, F5, F6, F7

Power Module (x3): Dynamic Brake

20A/600V

Mersen ATM20