Chapter 7, Specifications and dimensions, Table 12 - technical specifications 200 a prodysc – Rockwell Automation 1608P ProDySC User Manual, 200 A User Manual

Page 33: Ch 7 - specifications and dimensions, Chapter

Advertising
background image

Rockwell Automation Publication 1608P-UM003A-EN-P - September 2013

33

Chapter

7

Specifications and Dimensions

Table 12 - Technical Specifications 200 A ProDySC

Electrical Input/Output (Normal Mode—Static Switch)

Connection Configuration

Series-connected with load. Under normal line condition, the static switch passes utility voltage directly to the load

Standard Input Voltages

3-phase: 208, 380, 400, 415, 480V

1

Voltage Range

± 10%

Current Overload (Static Switch)

150% @ 30Sec., 400% @ 5 Sec., 600% @ 0.5 Sec.

Frequency

50/60 Hz Auto Sensing

Frequency Range

48 -62 Hz

TVSS

Output SPD, 25kA/mode. Protects L-L & L-G on all models; L-N & N-G (4-wire models)

Efficiency

> 99% @ 480V

Electrical Output (Sag Correction Mode - Inverter)

Output Voltage

Pre-sag rms voltage

Voltage Regulation

± 5% typical, +5 % / -13% of nominal max

ProDySC Output Current

200 A

RMS

2

Not rated for DC loads; max. allowable 2% DC loading

Crest Factor (at nameplate rms load)

1.45

Voltage Waveform

Sine wave

Voltage Sag Correction Times

Single Event

3 phase 87% to 50% Voltage Remaining

5 seconds

All three phases to zero voltage remaining

3 cycles, based on nameplate ratings with a power factor of 0.7, and frequency of 60Hz

Multiple Event

Max Sag Correction Time

5 seconds cumulative usage

Sequential Sag Recovery

0 seconds (assuming cumulative run-time available)

Full Recovery Time

Max 5 minutes

Mechanical

Enclosure Ratings

NEMA 1 (IP20)

Cable Entry

Top or Bottom

Cooling

Filtered Forced Air

Access

Front for servicing and connections

Audible Noise

less than 60 dBA at 1m

Weight

1470 lb (667 kg)

Environmental

Ambient Temperature

0 to 40°C

Storage Temperature

-40°C to 75°C

Relative Humidity

0 to 95% non-condensing

Altitude

Rated current available to 1000m (3300ft). De-rate output current 10% per 1000m, from 1000m to 3000m (9900ft).

Safety and Compliance

Agency Approvals

cULus Listed (UL 1012)

Standards Compliance

Exceeds SEMI F47 Standard; IEEE Std C62.41.1 and UL 1449 3rd Ed. compliant

1. ProDySC has not been evaluated for use in Corner Grounded or Ungrounded Delta Power Systems in systems rated over 240V.

2. When using ProDySC with motor drive loads, either insert 3% to 5% line reactance at ProDySC output or limit motor drive loads to 60% of ProDySC rating