Front side and user elements – Rockwell Automation 1606-XLE480EPC Power Supply Reference Manual User Manual

Page 11

Advertising
background image

Rockwell Automation Publication 1606-RM001B-EN-P - August 2013

11

Bulletin 1606 Switched Mode Power Supplies

13. Front Side and User Elements

Fig. 13-1: Fig. 13-1 Front side

A

Input Terminals (screw terminals)

N, L

Line input

PE (Protective Earth) input

B

Output Terminals (screw terminals, two pins per pole)

+ Positive output
Negative (return) output

C

Output voltage potentiometer
Open the flap to adjust the output voltage. Factory set: 24.1V

D

DC-OK LED (green)
On, when the output voltage is >90% of the adjusted output voltage

E

DC-OK Relay Contact (quick-connect spring-clamp terminals)
The DC-OK relay contact is synchronized with the DC-OK LED.
See

DC-OK Relay on page 7

for details.

F

“Parallel Use” “Single Use” selector
Set jumper to “Parallel Use” when power supplies are connected in parallel to increase the output power. In order to
achieve a sharing of the load current between the individual power supplies, the “parallel use” regulates the output
voltage in such a manner that the voltage at no load is approx. 4% higher than at nominal load.
See

Parallel Use to Increase Output Power on page 21

. A missing jumper is equal to a “Single Use” mode.

A

D

F

E

C

B

Advertising
This manual is related to the following products: