Dc-input, Input inrush current – Rockwell Automation 1606-XLE480EPC Power Supply Reference Manual User Manual

Page 5

Advertising
background image

Rockwell Automation Publication 1606-RM001B-EN-P - August 2013

5

Bulletin 1606 Switched Mode Power Supplies

4. DC-Input

Do not operate this power supply with DC-input voltage. Use Cat. No. 1606-XLE480EP-D instead.

5. Input Inrush Current

An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short input voltage interruptions.

The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.

*)

Mains interruptions > 500ms

AC 100V

AC 120V

AC 230V

Inrush current

*)

max.

13A

peak

13A

peak

13A

peak

temperature independent

typ.

11A

peak

9A

peak

7A

peak

temperature independent

Inrush energy

*)

max.

2A

2

s

2.5A

2

s

0.5A

2

s

temperature independent

Inrush delay

typ.

935ms

935ms

735ms

start-up delay plus rise time

Fig. 5-1: Typical input inrush current behavior

at nominal load and 25°C ambient

Output

100mS/DIV

Input

230Vac

24Vdc

Input Current 5A / DIV