Hold-up time, Dc-ok relay, Hold-up time 8. dc-ok relay – Rockwell Automation 1606-XLE480EPC Power Supply Reference Manual User Manual

Page 7

Advertising
background image

Rockwell Automation Publication 1606-RM001B-EN-P - August 2013

7

Bulletin 1606 Switched Mode Power Supplies

7. Hold-up Time

8. DC-OK Relay

This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit connected in
parallel to the power supply output.

AC 100V

AC 120V

AC 230V

Hold-up Time

typ.

65ms

65ms

65ms

at 24V, 10A, see

Figure 7-1

min.

54ms

54ms

54ms

at 24V, 10A, see

Figure 7-1

typ.

26ms

26ms

26ms

at 24V, 20A, see

Figure 7-1

min.

21ms

21ms

21ms

at 24V, 20A, see

Figure 7-1

Fig. 7-1:

Hold-up time vs. input voltage

Fig. 7-2: Shut-down behavior, definitions

Contact closes

As soon as the output voltage reaches 90% of the adjusted output voltage level.

Contact opens

As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.

Contact ratings

max.

60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A

resistive load

min.

1mA at 5Vdc

min. permissible load

Isolation voltage

Refer to

Dielectric Strength on page 14

.

Fig. 8-1: DC-ok relay contact behavior

Output
Current

0

42A

18s

18s

18s

2s

2s

2s

t

Short -circuit

Normal

operation

Normal

operation

Output Voltage (dynamic behavior, < 15ms)

0

0

4

8

12

28V

16

20

24

100A

40

20

60

80

10

30

50

70

90

Adjustment

Range

Output Current

0

10

20

30

40

80ms

90

120

155

190

230Vac

Input Voltage

50

60

Hold-up Time

24V, 20A, typ.

24V, 10A, min.

24V, 10A, typ.

70

24V, 20A, min.

- 5%

Hold-up Time

Zero Transition

Output
Voltage

Input
Voltage

100ms

0.9* V

ADJ

<

1ms

10%

open

V

OUT

= V

ADJ

open

closed

closed

>

1ms

Advertising