6. Output

Output voltage

nom.

24V

Adjustment range

min.

24-28V

guaranteed

max.

30V

****)

at clockwise end position of potentiometer

Factory settings

typ.

24.1V

±0.2%, at full load, cold unit, in “single use” mode

typ.

24.1V

±0.2%, at full load, cold unit, in “parallel use” mode

typ.

25.1V

at no load, cold unit, in “parallel use” mode

Line regulation

max.

10mV

85-300Vac

Load regulation

max.

100mV

in “single use” mode: static value, 0A

 20A;

see

Figure 6-1

typ.

1000mV

in “parallel use” mode: static value, 0A

 20A,

see

Figure 6-2

Ripple and noise voltage

max.

50mVpp

20Hz to 20MHz, 50Ohm

Output current

nom.

20A

at 24V, ambient temperature <60°C, see

Figure 6-1

nom.

24A

*)

at 24V, ambient temperature <45°C, see

Figure 6-1

nom.

17.1A

at 28V, ambient temperature <60°C, see

Figure 6-1

nom.

20.6A

*)

at 28V, ambient temperature <45°C, see

Figure 6-1

typ.

80A

up to 15ms, output voltage stays above 20V, see

Figure 6-4

, This peak current is

available once every five seconds. Refer to

Peak Current Capability on page 19

for

more peak current measurements.

Output power

nom.

480W

continuously available

nom.

576W

*)

Power Boost

® *)

Overload behaviour

cont. current

output voltage > 13Vdc, see

Figure 6-1

Hiccup

PLUS

mode

**)

output voltage < 13Vdc, see

Figure 6-1

Short-circuit current

min.

35A

***)

load impedance <10mOhm, see

Figure 6-3

max.

45A

***)

load impedance <10mOhm, see

Figure 6-1

max.

15A

***)

average (R.M.S.) current, load impedance 50mOhm, see

Figure 6-3

min.

70A

up to 15ms, load impedance <10mOhm, see

Figure 6-4

typ.

100A

up to 15ms, load impedance <10mOhm, see

Figure 6-4

Output capacitance

typ.

7 000μF

included inside the power supply

*)

Power Boost This power/ current is continuously allowed up to an ambient temperature of 45°C. Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.

**) Hiccup

PLUS

Mode At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the output is switched off for approx. 18s before a new start attempt is automatically

performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally. See

Figure 6-3

***) Discharge current of output capacitors is not included.
****) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not guaranteed value which can be achieved. The typical value is about 28.5V (in “single use” mode).

Fig. 6-1: Output voltage vs. output current, typ.

Fig. 6-2: Output voltage in “parallel use” mode, typ.

Fig. 6-3: Short-circuit on output, Hiccup

PLUS

mode, typ.

Fig. 6-4: Dynamic overcurrent capability, typ.

Output Voltage (Single Use, typ.)

0

0

25

4

8

12

28V

16

20

24

40A

15

5

10

20

30

35

Adjustment

Range

Output Current

Continuous

current

Factory

setting

Hiccup

mode

Output Voltage (Parallel Use, typ.)

22V

0

8

16

23V

24V

25V

29V

26V

27V

28V

24A

20

12

4

Adjustment

Range

Factory

setting

Output Current

Advertising