Ac-input – Rockwell Automation 1606-XLE480EPC Power Supply Reference Manual User Manual

Page 4

Advertising
background image

4

Rockwell Automation Publication 1606-RM001B-EN-P - August 2013

Bulletin 1606 Switched Mode Power Supplies

3.AC-Input

AC input

nom.

AC 100-240V

suitable for TN-, TT- and IT mains networks

AC input range

min.

100-264Vac

continuous operation

min.

85-100Vac

short term or with output derating (1%/V) or with reduced ambient temperature, see

Figure 15-1 on page 13

,

no damage between 0 and 100Vac

min.

264-300Vac

< 500ms

Allowed voltage L or N to earth

max.

300Vac

continuous, IEC 62103

Input frequency

nom.

50–60Hz

±6%

Turn-on voltage

typ.

84Vac

steady-state value, see

Figure 3-1

Shut-down voltage

typ.

39Vac

steady-state value at 5A load, see

Figure 3-1

typ.

53Vac

steady-state value at 10A load, see

Figure 3-1

typ.

74Vac

steady-state value at 20A load see

Figure 3-1

AC 100V

AC 120V

AC 230V

Input current

typ.

5.25A

4.36A

2.33A

at 24V, 20A, see

Figure 3-3

Power factor

*)

typ.

0.99

0.99

0.95

at 24V, 20A, see

Figure 3-4

Crest factor

**)

typ.

1.5

1.5

1.65

at 24V, 20A

Start-up delay

typ.

850ms

850ms

650ms

see

Figure 3-2

Rise time

typ.

85ms

85ms

85ms

at 24V, 20A const. current load, 0mF load capacitance,
see

Figure 3-2

typ.

150ms

150ms

150ms

at 24V, 20A const. current load, 20mF load
capacitance, see

Figure 3-2

Turn-on overshoot

max.

200mV

200mV

200mV

see

Figure 3-2

*)

The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.

**)

The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.

Fig. 3-1: Input voltage range

Fig. 3-2: Turn-on behaviour, definitions

Fig. 3-3: Input current vs. output load at 24V

Fig. 3-4: Power factor vs. output load

Tu

rn

-o

n

85V

Rated

input range

max.

500ms

V

IN

P

OUT

300Vac

264V

S

hut

-dow

n

Start-up

delay

Rise

Time

Ov

er

sh

o

o

t

- 5%

Output
Voltage

Input
Voltage

24A

2

4

6

8 10 12 14 16 18

0

1

2

3

4

5

6A

Input Current, typ.

20 22

a) 100Vac
b) 120Vac
c) 230Vac

b

a

c

Output Current

Power Factor, typ.

2

4

6

8 10 12 14 16 18

24A

0.75

0.8

0.85

0.9

0.95

1.0

20 22

a) 100Vac
b) 120Vac
c) 230Vac

a, b

c

Output Current

Advertising
This manual is related to the following products: