Chapter 4
Application Information

4–6

Discrete Inputs to the PLC–5

The discrete inputs to the PLC–5 are as follows:

Table 4.3

Octal Bit

Number

Decimal Bit

Number

Input Description

State Values

17

15

Module Status

1 = Module Failed

16

14

Raise Voltage

1 = Raise

15

13

Lower Voltage

1 = Lower

14

12

Raise Speed – Frequency Adjust

1 = Raise

13

11

Lower Speed – Frequency Adjust

1 = Lower

12

10

Raise Speed – Phase Adjust

1 = Raise

11

9

Lower Speed – Phase Adjust

1 = Lower

10

8

Raise Power – Load Share Adjust

1 = Raise

7

7

Reserved

N/A

6

6

Reserved

N/A

5

5

Reserved

N/A

4

4

Reduce Power – Load Share Adjust

1 = Lower

3

3

Close Breaker

1 = Close Breaker

2

2

Synchronization Failure

1 = Failure

1

1

Powered Up Bit

1 = Module Ready

0

0

Reserved

N/A

The Module Status discrete input to the PLC–5 when set to 1 indicates that
the LSM has identified a potential problem. A value of 0 indicates normal
operation of the LSM. Additional information pertaining to the cause of the
problem may be obtained by reading the appropriate block transfer data from
the “Diagnostic Parameters” Table B.11. (See Appendix B, “Block Transfer
Tables and Discrete I/O Definition”, for additional information.)

If the Module Status discrete input to the PLC–5 is set to 1, all block transfer
writes will be ignored and only the Diagnostic Parameters block transfer read
will return valid data. Any other block transfers should not be executed at
this time.

The Raise Voltage synchronization error discrete input to the PLC–5
indicates that the Synchronizing Bus has a lower voltage level than that of
the Reference Bus.

The Lower Voltage synchronization error discrete input to the PLC–5
indicates that the Synchronizing Bus has a higher voltage level than that of
the Reference Bus.

The Raise Speed – Frequency Adjust synchronization error discrete input to
the PLC–5 indicates that the Synchronizing Bus is producing voltage at a
frequency lower than that of the Reference Bus.

Interfacing to the LSM Continued