E - bulletin 1402 technical specifications, Bulletin 1402 technical specifications – Rockwell Automation 1402-LSM Line Synchronization Module Installation Instructions User Manual

Page 79

Advertising
background image

A–B

Appendix

E

E–1

Bulletin 1402 Technical Specifications

INPUTS:

Current

0 to 5A RMS Cont., 200A RMS 1 Second

Frequency

40 to 100 Hz (steady-state)

Dielectric Withstand Voltage

2500V RMS

Current Input Burden

0.05 VA

Voltage

120V RMS (339 Vpk-pk) Maximum Peak

Voltage Input Impedance/Burden

728K

W/0.02 VA

SYNCHRONIZATION WINDOW:

Independent Upper & Lower Thresholds

Voltage

0.05% steps

Frequency

0.01 Hz steps

Phase

1 degree steps

ISOLATED LOAD SHARING INPUT/OUTPUT:

Max. Common Mode Voltage

240V AC

Continuous Voltage

2 to 4V DC

Input Impedance

45K

W

BACK PLANE POWER REQUIREMENTS:

1.1A at 5V DC (2.2A, 5 ms Inrush)

ENVIRONMENTAL:

Operating Temperature

0

°

to +60

°

C

Storage Temperature

–40

°

to +100

°

C

Humidity

5% to 95%, non-condensing

UPDATE RATE:

Synchronizing Bus Error Parameters — 100 milli-seconds

Load Share and Monitor Parameters —

200 milliseconds (Synchronization Inactive)
1 second (Synchronization Active)

ACCURACY:

@ 25

_ C

Current Measurement= +/–0.2% of Full Scale (Full Scale=1.4 x CT Primary)

Voltage Measurement= +/–0.2% of Full Scale (Full Scale=1.25 x PT Primary)

Frequency Measurement= +/–0.05 Hz (Within the 47 to 63 Range)

Slip Frequency= +/–0.05 Hz (Within the 47 to 63 Range)

Power, Power Factor, VA= +/–0.4% of Full Scale Power Consumption

(Full Scale=1.75 x CT Primary x PT Primary)

CERTIFICATION

Agency Certification
(when product or packaging is marked)

CSA certified

CSA Class I, Division 2
Groups A, B, C, D certified

UL listed

CE marked for all applicable directives

Advertising