Front side and user elements – Rockwell Automation 1606-XLS960F-3 Power Supply Reference Manual User Manual

Page 14

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

14

Rockwell Automation Publication 1606-RM032A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

16. Front Side and User Elements

Fig. 16-1 Front side

A Input

Terminals

(Screw terminals)

L1, L2, L3

Line input

...PE (Protective Earth) input

B Output

Terminals

(Screw terminals, two pins per pole)

+

Positive output

– Negative (return) output

C “Parallel Use” “Single Use” Selector

Set jumper to “Parallel Use” when power supplies are
connected in parallel to increase the output power. In order
to achieve a sharing of the load current between the
individual power supplies, the “parallel use” regulates the
output voltage in such a manner that the voltage at no load
is approx. 4% higher than at nominal load. See also section
25.7. A missing jumper is equal to a “Single Use” mode.

D Output Voltage Potentiometer

Multi turn potentiometer;
Open the flap to set the output voltage.
Factory set: 48.0V at full output current, “Single Use” mode.

E DC-OK

LED

(green)

On, when the voltage on the output terminals is >90% of the
adjusted output voltage.

F Overload

LED

(red)

- On, when the voltage on the output terminals is <90% of
the adjusted output voltage, or in case of a short circuit in
the output.
- Flashing, when the shut-down has been activated or the
unit has switched off due to over-temperature.
- Input voltage is required.

G DC-OK

Relay

Contact

The DC-OK relay contact is synchronized with the DC-OK LED.
See section 8 for details.

H Shut-down and Remote Control Input

Allows the power supply to be shut down. Can be activated
with a switch contact or an external voltage.
The remote control input allows adjusting the output voltage
between 28V and 54V. See sections 9 and 10 for details.

Indicators, LEDs

Overload LED

DC-OK LED

DC-OK Contact

Normal mode

OFF

ON

Closed

During BonusPower

OFF

ON

Closed

Overload (Vout < 90%)

ON

OFF

Open

Output short circuit

ON

OFF

Open

Temperature Shut-down

flashing

OFF

Open

Active Shut-down input

flashing

OFF

Open

No input power

OFF

OFF

Open

A

B

C

D

E

F

G

H