All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

16

Rockwell Automation Publication 1606-RM032A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

Switching Frequencies

The power supply has three converters with three different switching frequencies
included. One is nearly constant. The others are variable.

Switching frequency 1

105kHz

Resonant converter, nearly constant

Switching frequency 2

1kHz to 150kHz

Boost converter, load dependent

Switching frequency 3

40kHz to 300kHz

PFC converter, input voltage and load dependent


18. Environment

Operational temperature

*)

-25°C to +70°C (-13°F to 158°F)

reduce output power according Fig. 18-1

Storage temperature

-40 to +85°C (-40°F to 185°F)

for storage and transportation

Output de-rating

24W/°C

60-70°C (140°F to 158°F)

Humidity

**)

5 to 95% r.H.

IEC 60068-2-30

Vibration sinusoidal

2-17.8Hz: ±1.6mm; 17.8-500Hz: 1g

***)

2 hours / axis

IEC 60068-2-6

Shock

15g 6ms, 10g 11ms

***)

3 bumps / direction, 18 bumps in total

IEC 60068-2-27

Altitude

0 to 2000m (0 to 6 560ft)

without any restrictions

2000 to 6000m (6 560 to 20 000ft)

reduce output power or ambient temperature,
see Fig. 18-2
IEC 62103, EN 50178, overvoltage category II

Altitude de-rating

60W/1000m or 5°C/1000m

> 2000m (6500ft), see Fig. 18-2

Over-voltage category

III

IEC 62103, EN 50178, altitudes up to 2000m

II

altitudes from 2000m to 6000m

Degree of pollution

2

IEC 62103, EN 50178, not conductive

LABS compatibility

The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.

*) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the

unit. Curves and figures for operation on only 2 legs of a 3-phase system can be found in section 25.4.

**) Do not energize in the presence of condensation.
***) Higher levels allowed when using the 1606-XLC wall mounting bracket.

Fig. 18-1 Output current vs. ambient temp.

Fig. 18-2 Output current vs. altitude

Allowed Output Current at 48V

0

-25

0

20

40

70°C

5

10

15

20

25

30A

continuous

60

Ambient Temperature

short-term (4s)

Allowed Output Current at 48V

0

0

2000

4000

5

10

15

20

25

30A

continuous

6000m

Altitude

short-term (4s)

A

C

A... Tamb < 60°C

B... Tamb < 50°C

C... Tamb < 40°C

B