Output – Rockwell Automation 1606-XLS960F-3 Power Supply Reference Manual User Manual

Page 6

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

6

Rockwell Automation Publication 1606-RM032A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

6. Output

Output voltage

nom.

48V

Adjustment range

min.

48-54V

guaranteed

max.

56V

***)

at clockwise end position of potentiometer

Factory setting

typ.

48.0V

±0.2%, at full load, cold unit, in “single use” mode

typ.

46.0V

±0.2%, at full load, cold unit, in “parallel use” mode

typ.

48.0V

at no load, cold unit, in “parallel use” mode

Line regulation

max.

10mV

3x323-576Vac

Load regulation

max.

50mV

in “single use” mode: static value, 0A 20A, see Fig. 6-1

typ.

2000mV

in “parallel use” mode: static value, 0A 20A,
see Fig. 6-2

Ripple and noise voltage

max.

150mVpp

20Hz to 20MHz, 50Ohm

Output current

nom.

20A

continuously available at 48V, see Fig. 6-1 and Fig. 6-2

nom.

17.8A

continuously available at 54V, see Fig. 6-1 and Fig. 6-2

nom.

30A

short term (4s) available BonusPower

*)

, at 48V,

see Fig. 6-1, Fig. 6-2 and Fig. 6-4

nom.

26.7A

short term (4s) available BonusPower

*)

, at 54V,

see Fig. 6-1, Fig. 6-2 and Fig. 6-4

typ.

55A

up to 25ms, output voltage stays above 40V, see Fig.
6-4, This peak current is available once every second.
See section 25.2 for more peak current measurements.

Output power

nom.

960W

continuously available at 48-54V

nom.

1440W

*)

short

term

available

BonusPower

*)

at 48-54V

BonusPower

time

typ.

4s

duration until the output voltage dips, see Fig. 6-3

BonusPower

recovery time

typ.

7s

overload free time to reset power manager, see Fig. 6-5

Overload behavior

cont. current

see Fig. 6-1

Short-circuit current

**)

min.

20A

continuous, load impedance 50mOhm, see Fig. 6-1

max.

22A

continuous, load impedance 50mOhm, see Fig. 6-1

min.

30A

short-term (4s), load impedance 50mOhm, see Fig. 6-1

max.

34A

short-term

(4s),

load

impedance

50mOhm,

see

Fig.

6-1

typ.

26A

continuous, load impedance <10mOhm

max.

29A

continuous,

load

impedance

<10mOhm

Output capacitance

typ.

3 700μF

included in the power supply

*)

BonusPower, short term power capability (up to typ. 4s)

The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short-
term duration is hardware controlled by an output power manager. BonusPower is repeatedly available. Detailed information
can be found in section 25.1. If the power supply is loaded longer with the BonusPower than shown in the bonus-time diagram (see
Fig. 6-3), the max. output power is automatically reduced to 960W.

**)

Discharge current of output capacitors is not included.

***)

This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not
guaranteed value which can be achieved. The typical value is about 55V.

Advertising