Rockwell Automation 1336F Plus II Parameters User Manual

Page 11

Advertising
background image

1336 PLUSII Parameter Record

Machine #
Date programmed
Drive Serial #

Par #

Parameter Name

Minimum Value

Maximum Value

Factory Default

Programmed Value

150 4-20mA Loss Sel

Min/Alarm

Min/Alarm

Stop/Fault
Hold/Alarm
Max/Alarm
Pre1/Alarm

151 Maximum Speed

0 Hz

400 Hz

400 Hz

152 Encoder Type

Pulse

Quadrature

Quadrature

153 Motor Poles

Read Only

154 Anlg Out 0 Offst

Disabled

Disabled

Enabled

155 Flying Start En

Disabled

Disabled

Speed Search
Use Encoder
Track Volts

156 FStart Forward

0 Hz

400 Hz

60 Hz

157 FStart Reverse

0 Hz

400 Hz

0 Hz

158 CR1 Out Select

Fault

At Speed

Alarm
Running
At Speed
At Freq
At Current
At Torque
Current Lmt
Mtr Overload
Line Loss
Drive Power
Drive Ready
Forward Run
Reverse Run
Braking
Economize
Auto Reset
At Temp
PI Max Error
Remote

159 Dig Out Freq

0.00 Hz

Programmed [Maximum Freq]

0.00 Hz

160 Dig Out Current

0%

200%

0%

161 Dig Out Torque

0.0 Amps

200% of [Rated Amps]

0.0 Amps

162 Torque Current

-200% Drive Rating

+200% Drive Rating

Read Only

163 Flux Current

-200% Drive Rating

+200% Drive Rating

Read Only

164 Speed KP

0

20000

0

165 Speed KI

0

20000

100

166 Speed Error

-8.33% of [Base Frequency]

+8.33% of [Base Frequency]

Read Only

167 Speed Integral

-8.33% of [Base Frequency]

+8.33% of [Base Frequency]

Read Only

168 Speed Adder

-8.33% of [Base Frequency]

+8.33% of [Base Frequency]

Read Only

169 Boost Slope

1.0

8.0

1.5

170 Rated Amps

Read Only

171 Rated kW

Read Only

172 EEPROM Cksum

Read Only

173 Fault Alarms 1

Bus Charging
Hardware Current Limit
Motoring Current Limit
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Mtr Overload
Motor Stalled
Ground Warning
Auxiliary Input
Heatsink Temp
Sync Loss
Phase Loss
4-20mA Loss
Motor OL Trip
Auto Reset

174 CR2 Out Select

Fault

Running

Alarm
Running
At Speed
At Freq
At Current
At Torque
Current Lmt
Mtr Overload
Line Loss
Drive Power
Drive Ready
Forward Run
Reverse Run
Braking
Economize
Auto Reset
At Temp
PI Max Error
Remote

Page 6 of 13

Advertising