1336 PLUSII Parameter Record

Machine #
Date programmed
Drive Serial #

Par #

Parameter Name

Minimum Value

Maximum Value

Factory Default

Programmed Value

206 Alarm Mask 1

Bus Charging

1111111111111111

Hardware Current Limit
Motoring Current Limit
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Mtr Overload
Motor Stalled
Ground Warning
Auxilliary Input
Heatsink Temp
Sync Loss
Phase Loss
4-20 mA Loss
Motor OL Trip
Auto Reset

207 Fault Data

1

255

Read and Write

208 Time Data 1
209 Time Data 3
210 Time Data 5
211 Time Data 7
212 DC Bus Memory

Read Only

213 PI Config

Inv Error - Changes sign of PI Error

00000000

Reset Int - Holds K1 at zero
Zero Clamp - Prevents bidirectional operation
Sqrt Fdbk-Uses sq. root of PI feedback value
Set Output
Preload Int
PI Enable
Spare

214 PI Status

Enabled

Read Only

Spare
Spare
Spare
Spare
Spare
Spare
Spare

215 PI Ref Select

Use Last

Preset 1

Analog In 0
Analog In 1
Analog In 2
Pulse Ref
MOP
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Preset 6
Preset 7
Encoder

216 PI Fdbk Select

Use Last

Analog In 1

Analog In 0
Analog In 1
Analog In 2
Pulse Ref
MOP
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Preset 6
Preset 7
Encoder

217 PI Reference

-400.00 Hz

400.00 Hz

Read Only

218 PI Feedback

-400.00 Hz

400.00 Hz

Read Only

219 PI Error

-400.00 Hz

400.00 Hz

Read Only

220 PI Output

-400.00 Hz

400.00 Hz

Read Only

221 KI Process

0

1024

128

222 KP Process

0

1024

256

223 PI Neg Limit

-400.00 Hz

400.00 Hz

-8.33% of [Maximum Freq]

224 PI Pos Limit

-400.00 Hz

400.00 Hz

+8.33% of [Maximum Freq]

225 PI Preload

-8.33% of [Maximum Freq]

+8.33% of [Maximum Freq]

0.00 Hz

226 Shear Pin Fault

Disabled

Disabled

Enabled
Not Accel

227 Adaptive I Lim

Disabled

Enabled

Enabled

228 LLoss Restart

Speed Search

Track Volts

Use Encoder
Track Volts
Last Speed

229 Freq Ref SqRoot

Disabled

Disabled

Enabled

230 Save MOP Ref

Disabled

Disabled

Enabled

Page 8 of 13