Rockwell Automation 1336F Plus II Parameters User Manual

Page 17

Advertising
background image

1336 PLUSII Parameter Record

Machine #
Date programmed
Drive Serial #

Par #

Parameter Name

Minimum Value

Maximum Value

Factory Default

Programmed Value

270 Latched Alarms 2

Motor Therm
Load Loss
Encoder Loss
Enc Cnt Set
Enc Cnt Max
Voltage Check
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused

271 Alarm Mask 2

Motor Therm

1111111111111111

Load Loss
Encoder Loss
Enc Cnt Set
Enc Cnt Max
Voltage Check
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused

272 Meas. Volts

0

200% Rated Drive Output Voltage

Read Only

273 Meas. D Volts
274 Anlg Out 1 Sel

Frequency

Current

Current
Torque
Power
Voltage
% Motor OL
% Drive OL
Encoder
Speed Error
PI Reference
PI Feedback
PI Error
PI Output

275 Anlg Out 1 Lo

-300.0%

+300.0%

0.0%

276 Anlg Out 1 Hi

-300.0%

+300.0%

100.0%

277 Anlg Out 1 Abs

Disabled

Enabled

Enabled

278 Anlg Out 1 Offst

Disabled

Disabled

Enabled

279 Elapsed Run Time

0

6553.5

0

280 Pulse Out Select

Output Freq

Frequency

Encoder Freq
Acc/Dec Freq

281 Pulse Out Scale

1

64

1

282 Enc Count Scale

1

4096

1000

283 Encoder Counts

-32767

+32767

0

284 Encoder Loss Sel

Disable

Disabled

Enable

285 Spare
286 Fault Status 2

At Freq
At Current
At Torque
Current Lmt
Mtr Overload
Line Loss
Drive Power
Drive Ready
Forward Run
Reverse Run
Braking
Economize
Auto Reset
At Temp
PI Max Error
Startup

287 Fault Alarms 2

Motor Therm
Load Loss
Encoder Loss
Enc Cnt Set
Enc Cnt Max
Voltage Check
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused

288 Bus Regulation

Disabled

Disabled

Enabled

289 Spare
290 Load Loss Detect

Disabled

Disabled

Alarm
Fault

Page 12 of 13

Advertising