1336 PLUSII Parameter Record

Machine #
Date programmed
Drive Serial #

Par #

Parameter Name

Minimum Value

Maximum Value

Factory Default

Programmed Value

38 Overload Amps

20% of Drive Rated Amps

115% of Drive Rated Amps

115% of Drive Rating

39 Flt Clear Mode

Disabled

Enabled

Enabled

40 Line Loss Fault

Disabled

Disabled

Enabled

41 Motor Type

Induction

Induction

Sync Reluc
Sync PM

42 Slip @ F.L.A.

0.0 Hz

10.0 Hz

1.0 Hz

43 Dwell Frequency

0.0 Hz

7.0 Hz

0.0 Hz

44 Dwell Time

0 Sec

10 Sec

0 Sec

45 PWM Frequency

1 KHz

A & B Frame Drives = 8 kHz

2 KHz

C Frame Drives & Up = 6 kHz

46 Encoder PPR

1

4096

1024 PPR

47 Language

English

English

FRANCAIS
ESPANOL
Italiano
Deutsch
Japanese
Portuguese
Nederlands

48 Start Boost

0 Volts

9.5% of Drive Rated Voltage

0 Volts

49 Break Frequency

0 Hz

120 Hz

25% of [Maximum Freq]

50 Break Voltage

0 Volts

50% of Drive Rated Voltage

25% of Drive Rated Voltage

51 Clear Fault

Ready

Ready

Clear Fault

52 Stop Select 2

Coast

Coast

DC Brake
Ramp
S Curve
Ramp to Hold

53 DC Bus Voltage

0

200% DC Bus Voltage Max

Read Only

54 Output Current

0

200% Rated Drive Output Current

Read Only

55 Input Status

Input 1 - TB3-19
Input 2 - TB3-20
Input 4 - TB3-23
Input 3 - TB3-22
Input 5 - TB3-24
Input 6 - TB3-26
Input 8 - TB3-28
Input 7 - TB3-27

56 S Curve Time

0.0 Sec.

1800.0 Sec

0.0 Sec

57 S Curve Enable

Disabled

Disabled

Enabled

58 Common Bus

Disabled

Disabled

Enabled

59 Drive Status 1

Enabled
Running
Command Direction
Actual Direction
Accelerating
Decelerating
Alarm
Faulted
At Speed
Local Adapter ID
Local Adapter ID
Local Adapter ID
Reference ID
Reference ID
Reference ID
Reference ID

60 Drive Alarm 1

Bus Charging
Hardware Current Limit
Motoring Current Limit
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Mtr Overload
Motor Stalled
Ground Warning
Auxilliary Input
Heatsink Temp
Sync Loss
Phase Loss
4-20 mA Loss
Motor OL Trip
Auto Reset

61 Drive Type

Read Only

62 Freq Source

Use Last

Use Last

Analog In 0
Analog In 1
Analog In 2
Pulse Ref
MOP
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Preset 6
Preset 7
Encoder
Jog Sel

Page 2 of 13

Advertising