MegaDySC System Installation Connections Checklist

Connect the Automatic Bypass Switchboard ground bus to an earth
ground in accordance with the National Electrical Code and local codes.

Connect the AC input (line) conductors to the terminals labeled “R in”,
“S in”, and “T in”. The set is labeled “UTILITY INPUT”. See

Figure 13

.

Connect the AC output (load) conductors to the terminals labeled “R
out”, “S out” and “T out”. The set is labeled “PROTECTED LOAD”. See

Figure 13

.

For 4-wire models only: connect input and output Neutral (N) conductors
to the NEUTRAL bus bar. The input N connection is required for proper
operation of 4-wire models.

Check all electrical terminations for properly torqued connections.

For i-Sense and MegaDySC communications: connect an Ethernet cable
to the Ethernet switch located in the upper left compartment of the
Automatic Bypass Switchboard. Refer to

Chapter 3

-

Communications on

page 21

for details.

For remote status indication via dry contacts, connect to the “TB1”
terminal block located in the upper left compartment of the Automatic
Bypass Switchboard. Refer to

Chapter 3

-

Communications on page 21

for

details.