Installation and Wiring

3-11

1503-UM052D-EN-P – June 2013

The IntelliVAC can be applied with two- or three-wire control circuits.

The control system utilized will determine the configuration of the input

wiring. Consider the following input and output for the type of control
used:

• Terminals 9 and 10 – Close Contactor

• Terminals 15 and 16 – Contactor Status

In either case, the CLOSE input must receive a maintained voltage high

to keep the contactor closed.

Note:

1. When used with electrically held contactors, the IntelliVAC allows

close commands every six seconds. This is to ensure the rated

contactor duty cycle is not exceeded.

2. If IntelliVAC powers up configured for an electrically held contactor,

and the vacuum contactor is detected as being closed, the module will

not respond to a close command until the vacuum contactor auxiliary

contact input is in the correct (closed) state and module power is
removed and re-applied. (See Chapter 5)

3. In general, a Close command should only be applied 4 seconds after

energizing IntelliVAC.

A T T E N T I O N

A T T E N T I O N

For Emergency Stop applications requiring
removal of power, a contact should be placed in

the “L1” control power rung to the IntelliVAC.

If the TDUV feature is used, the contactor will
not open until the programmed TDUV time

has expired.

Wiring Guidelines Electrically

Held Contactors