Rockwell Automation 1503 IntelliVAC Contactor Control Module - Series C and later User Manual

Page 50

Advertising
background image

Typical Contactor Drop-out Times

A-3

1503-UM052D-EN-P – June 2013

Table A.1 – Typical Contactor Drop-out Time Settings (cont.)

Fuse Rating

Contactor Drop-out Time Setting (msec)

Voltage

Designation

400A

800A

7200

2R

50

50

3R

4R

6R

9R

12R

18R

75

24R

150

32R

240 *

38R

75

48X

150

57X

200

2 x 18R

50

2 x 24R

130

2 x 32R

240 *

2 x 38R

2 x 48X

2 x 57X

8250

10E

50

50

15E

20E

25E

30E

40E

50E

65E

80E

100E

125E

150E

175E

200E

Fuse not suitable for use with contactor.

Note: The drop-out time is chosen to be equal to or greater than the

intersection of the rated contactor interrupting current and the

fuse melt time curve (except where noted *)

Advertising