Typical Contactor Drop-out Times
A-3
1503-UM052D-EN-P – June 2013
Table A.1 – Typical Contactor Drop-out Time Settings (cont.)
Fuse Rating
Contactor Drop-out Time Setting (msec)
Voltage
Designation
400A
800A
7200
2R
50
50
3R
4R
6R
9R
12R
18R
75
24R
150
32R
240 *
38R
⊇
75
48X
⊇
150
57X
⊇
200
2 x 18R
⊇
50
2 x 24R
⊇
130
2 x 32R
⊇
240 *
2 x 38R
⊇
⊇
2 x 48X
⊇
⊇
2 x 57X
⊇
⊇
8250
10E
50
50
15E
20E
25E
30E
40E
50E
65E
80E
100E
125E
150E
175E
200E
⊇
Fuse not suitable for use with contactor.
Note: The drop-out time is chosen to be equal to or greater than the
intersection of the rated contactor interrupting current and the
fuse melt time curve (except where noted *)