Setup and Commissioning

4-3

1503-UM051C-EN-P – June 2005

Table 4.A – DIP Switch Factory Default Settings

DIP switch

Description

1

2

3

4

5

6

7

8

9

10

11

12

Altitude: 0 – 1000m

0

0

1

Drop-out time: 130 msec

0

1

1

Contactor config.: 400A EH

0

1

TDUV config.: No TDUV

0

Ext. cap TDUV time: 0.2 sec

0

0

Power-Up Safety: Enable

0

IntelliVAC units shipped in a complete MV controller (Bulletin

1500/1900) will be configured to suit the installed application (i.e.
contactor type). The user should verify the settings before energizing the

equipment. Table 4.B defines the settings for each switch.

Table 4.B – IntelliVAC DIP Switch Explanation

UP = 1

DOWN = 0

DIP switch SW1

1

2

3

4

5

6

7

8

9

10 11 12

|

|

|

|

Altitude

1

2

3

12

Power-Up Safety

-1000 to 0

0

0

0

0

Enable

1 to 1000

0

0

1

1

Disable

1001 to 2000

0

1

0

2001 to 3000

0

1

1

10

11

Ext. cap. TDUV time

3001 to 4000

1

0

0

0

0

0.2 sec

4001 to 5000

1

0

1

0

1

0.5 sec

Not defined

1

1

0

1

0

1.0 sec

Not defined

1

1

1

1

1

2.0 sec

9

TDUV config.

0

No TDUV

Drop out time

4

5

6

1

TDUV Enabled

50 msec

0

0

0

75 msec

0

0

1

7

8

Contactor Config.

100 msec

0

1

0

0

0

400A Mech. Latch

130 msec

0

1

1

0

1

400A Elec. Held

150 msec

1

0

0

1

0

800A Mech. Latch

175 msec

1

0

1

1

1

800A Elec. Held

200 msec

1

1

0

240 msec

1

1

1

The altitude compensation by DIP switch settings applies to Series E 400 amp vacuum contactors only. All 800 amp contactors are adapted

for altitude by altering the return springs. 800 amp contactors are to be set for 1 to 1000m (001 DIP setting).

Advertising