Typical Contactor Drop-out Time Settings

The contactor drop-out time settings shown in the following table are

typical minimum values used when the power fuses are provided as part of

a complete MV controller from Rockwell Automation. The

recommendations are based on Ferraz-Shawmut power fuses. Other fuse
types may require alternate drop-out time settings.

The IntelliVAC module DIP switches are set up to provide the minimum

drop-out times shown (refer to Chapter 4).

Table A.1 – Typical Contactor Drop-Out Time Settings

Fuse Rating

Contactor Drop-out Time Setting (msec)

Voltage

Designation

400A

800A

< 5000

2R

50

50

3R

4R

6R

9R

12R

18R

19R

24R

100

32R

240

38R

48X

75

57X

200

2 x 24R

100

2 x 32R

240 *

2 x 38R

2 x 48X

2 x 57X

Fuse not suitable for use with contactor.

Note: The drop-out time is chosen to be equal to or greater than

the intersection of the rated contactor interrupting current and

the fuse melt time curve (except where noted * ).