All parameters are specified at 24V, 2.1A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM034A-EN-P — March 2014

15

Bulletin 1606 Switched Mode Power Supplies

23. Physical Dimensions and Weigth

Weight 240g / 0.53lb

DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.

The DIN rail height must be added to the de pth (91mm) to calculate the total required
installation depth.

Fig. 23-1 Front view

Fig. 23-2 Side view

24. Installation and Operation Instructions

Mounting:
Output terminal must be located on top and input terminal on the bottom. For other orientations, see section 26-12.
An appropriate electrical and fire end-product enclosure should be considered in the end use application.
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grille (e.g. cable conduits) by more than 30%!
Installation clearances:
25mm on top and bottom.
Risk of electrical shock, fire, personal injury or death!
Do not use the unit without proper ground connection (Protective Earth).
Turn power off before working on the power supply. Protect against inadvertent re-powering.
Make sure the wiring is correct by following all local and national codes.
Do not open, modify or repair the unit.
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where moisture or condensation is likely to occur.
Service parts:

The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal fault. Should
damage or malfunction occur during operation, turn power off immediately and return the unit to the factory for
inspection!