All parameters are specified at 24V, 2.1A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

6

Rockwell Automation Publication 1606-RM034A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

8. Hold-up Time

AC 100V

AC 120V

AC 230V

Hold-up

Time

typ.

54ms

82ms

360ms

1.05A, 24V, see Fig. 8-1

typ. 26ms 40ms 180ms 2.1A, 24V, see Fig. 8-1

Fig. 8-1 Hold-up time vs. input voltage

Fig. 8-2 Shut-down behavior, definitions

0

20

40

100

120ms

85

120

155

190

230Vac

Input Voltage

Hold-up Time

60

80

a) 24V 1.05A typ.
b) 24V 1.05Amin.
c) 24V 2.1A typ.
d) 24V 2.1A min.

a

b

c

d

- 5%

Hold-up Time

Zero Transition

Output
Voltage

Intput
Voltage

Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on at this time.

9. DC-OK Output

This feature monitors the output voltage, which is present on the output terminals.
The signal is a source output which can feed loads up to 30mA. Loads can be a 24V relay (Rcoil < 700Ohm), a LED or
the input of a PLC system. The relays operates or the LED is on if output voltage exceeds the threshold level.
A wheeling diode (necessary when the load is a relay) is already included in the power supply.

Threshold value

20V +/-4%

Output current

min.

30mA

For typical values see Fig. 9-2

Output voltage

min

Vout – 1V

at 30mA

The open collector is internally linked to the positive output pole. The
DC-OK voltage is approximately the output voltage if the output voltage
is higher than the threshold level.

Fig. 9-1 DC-ok wiring diagram

Fig. 9-2 Output characteristic DC-OK signal

+ +

DC

ok

-

-

24-28V

N L

DC-ok

Relay

LED

DC-OK Voltage

0

0

10

20

4

8

12

28V

16

20

24

40m A

25

15

5

30

35

DC-OK Current

-

DC

OK

-

+

+

ML50

V

A

Load

Test Setup