All parameters are specified at 24V, 2.1A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM034A-EN-P — March 2014

9

Bulletin 1606 Switched Mode Power Supplies

12. Functional Diagram

Fig. 12-1 Functional diagram

Input Fuse
&
Input Filter

L

N

Output Over-

Voltage

Protection

DC-OK

Transistor

Signal

Input
Rectifier
&
Inrush
Limiter

Power

Converter

Output

Voltage

Regulator

+

+

-
-

Output

Filter

V

OUT

DC

ok

DC-ok

Signal

13. Reliability

These units are extremely reliable and use only the highest quality materials. the number of critical components such
as electrolytic capacitors has been reduced.

AC 100V

AC 120V

AC 230V

Lifetime expectancy

min. 34,000h 44,000h 54,000h 40ºC, 24V 2.1A

min. 112,000h 117,000h 111,000h 40ºC, 24V, 1.05A
min. 96,000h 125,000h 152,000h 25ºC, 24V, 2.1A

MTBF SN 29500, IEC 61709 2,383,000h 2,456,000h 2,613,000h 40°C, 24V, 2.1A
3,977,000h 4,100,000h 4,362,000h 25ºC, 24V, 2.1A

MTBF MIL HDBK 217F 1,021,000h 1,053,000h 1,120,000h 40ºC, 24V, 2.1A, Ground Benign GB40
1,370,000h 1,413,000h 1,503,000h 25ºC, 24V, 2.1A, Ground Benign GB25

The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors.
Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to specifications
from the manufacturer of the capacitor. The prediction model allows a calculation of up to 15 years from shipping date.
MTBF

stands for Mean Time Between Failures; it is calculated according to statistical device failures and indicates

reliability of a device. It is the statistical representation of the likelihood of failure of a unit and does not necessarily
represent the life of a product.