Table 11 General Parameters

Parameter

Value

Input impedance Voltage input, per
phase

2 Mohm

Input load Current, 1A and 5A

0.02 ohm

Nominal voltage

per catalog number version

Units with separate 120V or 240V supply: 600V

Units powered from 400V measurement line: 400V

Units powered from 480V measurement line: 480V

Nominal current input

1 A or 5 A

Overload current rating Nominal
current input 5A

2 x, continuous

Temperature coefficient

< 0.01% / K

Temperature - Operating

+5 to +50°C (+41 to +122°F) (ambient)

Temperature - Storage

-20 to +70°C (-4 to +158°F)

Frequency range

47 to 63 Hz

Power consumption

Approx. 3 W

Weight

Approx. 0.3 kg

Front dimensions

96 x 96 mm

Breakdown rating

Per DIN 41700

Panel insertion depth

85 mm

Panel mounting fasteners

Screw clamps

Panel cutout dimensions

92 mm x 92 mm +/- 0.8 mm

Spacing between cutouts

4 mm (minimum), 20 mm (typical)

Protection class

Enclosure IP 20

(IP 65 with optional protective hood

(1)

(1)

The optional hood, catalog number 1405-PRO, can be ordered separately. Contact your Rockwell Automation
distributor for additional information.

)

Terminals IP 00

Agency Certifications

UL, CE

Table 12 Digital Displays

Type

7-segment LED, red

Lines x characters

3 x 5

Character height

14 mm

Publication 1405-IN002C-EN-P - November 2004