Publication 1405-IN002C-EN-P - November 2004

Bulletin 1405 (M620) Operating Instructions 3

1. Install your module within a suitable enclosure. Make sure the

enclosure provides adequate clearance for ventilation and wiring
of the module.

Refer to Dimensions on page 20 for dimensions and spacing
guidelines for the MiniPowermonitor.

2. Determine your wiring mode and install wiring between the

MiniPowermonitor and your power system.

Refer to Electrical Connections on page 3 for more information.

3. Configure the instrument settings to match those used in your

power system connections.

Refer to Instrument Set-Up on page 14 for more information.

Grounding

MiniPowermonitors do not need to be grounded because of the
isolated enclosures. Follow all local requirements for grounding of PT
and CT secondaries.

Electrical Connections

Electrical connections are terminated on two plug-in connector blocks
with spring-clamp wire terminals, at the rear of the instrument. These
connector blocks, 7- and 12-pin respectively, can accept wire sizes
from 28 to 14 AWG (0.08 to 2.5 sq.mm).