Table 13 Relay Outputs

Alarm

Logic: contacts open on alarm

Energy pulses

Contacts close: 128 ms / 128 ms

Energy pulse output rate

Selectable: 0.01, 0.10, 1.00, 10.0, 100
kWh/pulse (0.0 disables)

Contacts rating Voltage

250Vac; 220V dc

Load:

60 VA; 60 W

Table 14 Measurement Accuracy and Range

Parameter

Percent of Reading

Nominal Value

Operating Range

Maximum Limit

Volts

±1%

240V rms

10V rms to 347V rms L-N or
17V rms to 600V rms L-L

400V rms L-N or

690V rms L-L

Current

±1%

5 Amps

0.1 Amps to 8 Amps

10 Amps

Power and Energy

±2%

n/a

n/a

n/a

Power Factor

±0.2%

n/a

n/a

n/a

Table 15 Modbus Communications

Port specifications

RS-485, 2-wire, half-duplex

Protocol

Modbus RTU slave

Data Rate

9.6 or 19.2 Kbaud, selectable

Isolation

500 Vac, tested 1 kV ac

Publication 1405-IN002C-EN-P - November 2004

22 Bulletin 1405 (M620) Operating Instructions

Product Approvals

UL/CUL

cULus Listed, File E96956, per UL508, the Standard for Industrial
Control Equipment.

CE Certification

If this product bears the CE marking, it is approved for installation
within the European Union and EEA regions. It has been designed to
meet the following directives.

EMC Directive

This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole, documented in a technical construction file: