Module Programming
Chapter 4
4–6
4.
Apply power to the I/O chassis. Enter the Block Transfer rung shown
in Figure 4.6 into the PLC–5/15 processor.
Figure 4.6
Block Transfer Rung for a PLC-5/15 Processor
NOTE: If the module is installed in a physical slot other than the fifth slot
to the right of the PLC processor, the BTR block will have to be set up
with a Rack/Group/Slot address other than 020. Refer to Figure
4.3
for the
correct address settings.
5.
Place the PLC–5/15 processor into RUN mode.
Use the Data Monitor in the 6200 Series Software to examine data table
address N36:0. This is where the processor has stored the rates and total
counts received from the 1771–QRD.
Only the channels which are actually driven will be active.