Troubleshooting

Chapter 6

6–2

Symptom

Probable Causes

Possible Solutions

Data counts to small value,

then jumps to zero

Continuous BTW Reset

Check ladder program to be sure that

the block transfer write is not causing

continuous resets of the totalizer(s)

Rates and counts from one

input appear in more than

one channel position in the

data table

Wiring reversal of + and - inputs

Refer to wiring diagrams