Operational limits – Rockwell Automation 1771-QRD PULS FLOWMTR User Manual

Page 43

Advertising
background image

Specifications

Appendix B

B–2

Signal Characteristics, Turbine Flowmeter or Magnetic Pickup: 50 mV
to 142 VAC RMS

The signal should be approximately sinusoidal and must be AC. The signal
must be greater than 50 mV peak to peak, and must be smaller than 400 V
peak to peak.

Signal Characteristics, TTL: 1.3 V threshold

The signal should be DC pulses with width greater than 20 uS. The logic
“1” level must be greater than + 1.3 V and smaller than +200 V while the
logic “0” level must be larger than –.7V and smaller than +1.3V.

The TTL mode is compatible with TTL, 4,000 series CMOS, and most
0–24 V systems. The TTL mode is not compatible with any signal format
with DC pulses riding on a fixed DC level greater than + 1.3 V.

Note: Signal type is selectable by swing arm jumper. Channel thresholds
are jumpered in pairs.

Input Impedance: 5 kOhm

" 30% resistive, minimum

Isolation: 1000 V minimum between channels and microcontroller, and
between channel pairs

Accuracy: 0.1%

"1 Hz for frequency t 3.0 kHz 0.2% "1 Hz for

frequency

u 3.0 kHz

Overrange Indication: Individual bit for each channel set to indicate rate
above 10 kHz

Overflow Indication: Individual bit for each channel set to indicate total
above 32, 767

Overrange Response: When a channel signal exceeds 10 kHz the rate
overrange bit will be set, the total reset to zero, and the rate for that
channel reported as zero

Maximum Operating Frequency: 10.0 kHz for PLC–3 and PLC–5, 0.999
kHz for PLC–2 (New Use)

Total Control: Overflow bit and total can be cleared by ladder logic.
Clearing total also clears overflow bit

Operational Limits