2–2

Quick Start

Publication 1746-6.18 April 1998

4.

Connect Module Output Terminals to Output Devices With Correct Bonding

Chapter 4

1746-QV Output
Terminal Block

Analog Output
(

"10v dc)

Diff.
Input

Outputs
to valves

Servo Amplifier
(Proportional)

(+)

(–)

To solenoid A

To solenoid B

A

B

+24V dc PS
0V dc PS

Do NOT connect output
shields to earth ground

2
1

0V

Important: Connect the shield of the amplifier
output cable to a 0V connection in the amplifier.

5.

Minimize Interference from Electrical Noise with Correct Shielding and Grounding

Chapter 4

Important: Connect PS output commons togerther.
Connect the following to earth ground: a) cable shields (except for amplifier outputs) at one end only,
b) input terminal 4, c) case grounds of PS and amplifier, e) LDT flange.

1746-QV
Module

LDT and Hydraulic Ram

Analog Output

Valves

Servo
Proportional
Amplifier

LDT
Signals

24V PS

"15V PS

4

earth ground

2

(–) (+)

(+) (C) (–)

Output

Input

Belden
8761

Belden
8761

Case
GND

Case
GND

Cable
Note

Cable
Note

Cable Note: Use cable
recommended by the LDT
and amplifier manufacturer.

Belden
8770

3

1

5-8

LDT
Power

Piston-type Hydraulic Cylinder and
Linear Displacement Transducer (LDT)

0V

Case
GND

2

1

Important: For correct bonding,
connect PS output commons together
and isolate from earth ground.

6.

Operate the Module for the First time

Chapter 5

After loading profiles with the ladder program (step 1), alternately run the extend profile (O:e.0/0 = 0-to-1),
then the retract profile (O:e.0/1 = 0-to-1). Modify the profile to reach the preset reference, and set it.
Important:
If motion is reversed: for a

"10V dc output, change the sign (") of all extend/retract voltage

values; or for a +10V output, energize the other solenoid on the directional valve (with ladder logic).

To do this:

Enter decimal:

at address:

load all profiles

1

N7:40

set preset reference to zero

8

N7:50

clear errors

16

N7:50

read current position

read, only

N7:61

run an extend profile

1

N7:50

run a retract profile

2

N7:50