Modify n files in your slc processor, off-line, Output image table with profile data, Command and position setpoints for extend #n7:0 – Rockwell Automation 1746-QV,D17466.18 OPEN-LOOP VELOCITY CONTL User Manual

Page 14: Command and position setpoints for retract #n7:20

Advertising
background image

3–4

Setting Up the Software

Publication 1746-6.18 April 1998

One N file may contain the initial commands, setpoints, and values
for configuring the extend and retract profiles.

Output Image Table

>>>

Command
and
Setpoints

Retract Voltages

Retract Positions

Extend Voltages

Extend Positions

A set of profile data
for initial configuration

Command
and
Setpoints

>>>

>>>
>>>

1746-QV Module

Extend
and Retract
Profiles

>>>

>>>

>>>
>>>

The file contains commands and data starting at the these addresses:

command and position setpoints for extend

#N7:0

command and voltage (velocity) values for extend #N7:10

command and position setpoints for retract

#N7:20

command and voltage (velocity) values for retract

#N7:30

The sample ladder program (appendix B) copies profile data into the
output image table from the above locations.

Output Image Table with Profile Data

Word:

Function of Output Image Word:

Bit #:

Description: (For command bits, a 0-to-1 transition enables the command)

0

Command Bits

0

Set to run an extend profile.

Co

and Bit

Enable the e bit

e. /bit

1

Set to run a retract profile.

Enable these bits (O:e.0/bit #)
with our ladder logic where e

2

Set to disable the profile. This bit over-rides bit 0 or 1.

with your ladder logic, where e
represents the I/O slot number.

3

Set to change the current position data to the value of the preset reference
stored in Ge:6.

4

Set to clear any data-entry errors.

5

Set to define words 1-7 as programmed position setpoints for extend.

6

Set to define words 1-7 as programmed voltage values for extend.

7

Set to define words 1-7 as programmed position setpoints for retract.

8

Set to define words 1-7 as programmed voltage values for retract.

9-15

Reserved. Do NOT use.

1-7

Position Setpoint or Voltage Value

n/a

Important: Position setpoints are in units of 0.01” (200 = 2.00”)
within the range of –327.68” to +327.67”, and voltage values in
5mV units (3005 = 3.005V) within the range of

"10,000mV.

The data monitor mode of your programming software displays the
data files shown below (with values from the ladder program).

Important: Modify these values to suit the preset reference chosen
for the G file and/or to match the LDT length.

Extend Positions:

N7:0

32

–45

50

200

300

400

425

500

0

0

Extend Velocities:

N7:10

64

3000

3750

4000

4000

4000

4000

4000

0

0

Retract Positions:

N7:20

128

–45

50

200

300

400

425

500

0

0

Retract Velocities:

N7:30

256

5000

6000

6000

3000

1000

50

25

0

0

Modify N Files in Your