3–2

Setting Up the Software

Publication 1746-6.18 April 1998

5. Download ladder program VELMOD (65 Kbyte SLC code) into the

subdirectory on your hard drive where your programming software
looks for files. With RSLogix: C:\ . . . RSLogix 500 English\Project.

6. Download the ladder program to your SLC processor.

7. Download the manual into a hard drive subdirectory. You must

decompress the Word version with PKUNZIP

available on BBS.

To Access the Internet:

1. Access the Allen-Bradley webpage at:

http://www.ab.com

2. To access the member area, you must log in. If you do NOT have

an account, click Join Now and follow the prompts to register.

3. Search for QV: on homepage, click Search Our Site, insert QV into

the window, and click Search button. The manual is PDF format and
requires Adobe Acrobat

viewer. The ladder program is PDF format

and must be entered manually.

This procedure assumes you are using RSLogix500

Programming Soft-

ware, version 2.10 or later. For other software, the procedure may vary.

1. Open your 1746-QV project,

VELMOD

.

2. Configure the type of SLC processor. To do this:

A. Open the file, Controller Properties.

B. Select the SLC processor type and click OK.

3. Configure the rack size, module slot, and module ID:

A. Open the file, I/O Configuration.

B. Select the rack size.

C. Highlight the slot number for the module.

D. From the list of modules, scroll to 1746-QV and double–click.

If the module is not listed:
– Scroll to Other and double-click.
– Enter the module’s ID (13115) and double-click.

4. Size the “G” file:

A. Highlight 1746-QV (or 13115 if module was not listed).

B. Click [Adv Config].

C. In the dialog box, enter a G-file length of 7.

D. Press [Edit G Data].

Configuring Your
SLC Processor, Off-line