3–3

Setting Up the Software

Publication 1746-6.18 April 1998

5. Enter values in the G file:

If the module was listed:

If the module was not listed (you entered the ID):

You get the G–file Setup screen.
Enter data from the table, below.

You get the following display, shown in decimal radix.
Enter a value in each word as shown, next.

G–file display for unlisted module (shown in decimal radix):

Ge:0

2056

0

0

0

0

0

0

Enter a value at each G-file word address and press

[ENTER]

.

Then cursor to the next word address and repeat. For example:

Ge:0

2056

893

730

12

1200

–32768

0

We used values from the ladder logic example (appendix B).
You will want to use G-file values that suit your application:

Word:

Function of G-file Word:

Range:

Description of G-file Word or Bit:

Example:

0

Reserved. Do NOT use.

n/a

The processor stores a code for the 1746-QV module.

2056

words 1 & 2 refer to the gradient or transducer calibration value stamped on the name plate on the transducer housing.

1

LDT calibration: upper 3 digits

800-999

ms/inch

For example: To enter an LDT calibration of 8.9373,
u e deci al radi and enter 893 in word 1 and 73 in word 2.

893

2

LDT calibration: lower 3 digits

000-999

ms/inch

For e a ple o enter an

calibration of 8.9373

use decimal radix and enter 893 in word 1 and 730 in word 2.

730

3

Full-scale length (L) of LDT

2

vLv160 inch

Enter the length of the LDT (160 inches max).

12

4

Full-scale count (C)

2

vCvLx100

Typically C = L x 100.

Position Data (I:e.1) = C/(L x 100)

LDT Calibration

1200

5

Configuration Bits

bits 0-12

Set to zero.

–32,768

bit 1 = 1

Configuration Bit

15 14 13 12-0 Equivalent Value
0 1 0 0

+16,384

1 0 0 0

–32,768

1 1 0 0

–16,384

bit 13

0 = output maintained during LDT fault while running profiles and

during SLC mode change

1 = output resets for LDT fault and SLC mode change

–32,768

(bit 15 = 1
for position
increases
towards

head

1 1 0 0

–16,384

0 1 1 0

+24,576

bit 14

Type of LDT: 0 for RPM, 1 for DPM

towards
LDT head)

bit 15

0 = position data increases when moving away from LDT head
1 = position increases when moving toward LDT head

6

Preset Reference

–32,768 to +32,767 Typically zero or home reference value. 32,767 = 327.67 inches.

0

Examples of Full-scale Count Values

LDT Physical
Length

No. of
Recirculations

Resolution

Full-scale
Length (L)

Full-scale
Counts (C)

from 160” to 2”

1

0.01

L (160” to 2”)

L x 100

16”

2

0.01

160

8000

16”

4

0.01

160

4000

16”

10

0.001

160

16000

Important: The module checks for invalid data such as out of
range values or the setting of reserved bits 0-12. You can clear a
data-entry configuration error only by re-entering a corrected value.

6. Save when done

.

Click OK. Click OK. Close window.