Rockwell Automation 1734-OB2EP Point I/O Protected Output Module Installation Instructions User Manual

Page 12

Advertising
background image

12 POINT I/O Protected Output Module

Publication 1734-IN586A-EN-P - December 2001

Indication

Probable Cause

Network Status

Off

Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator

Flashing Green

Device is on-line but has no connections in the established
state.

Green

Device on-line and has connections in the established state.

Flashing Red

One or more I/O connections in timed-out state

Red

Critical link failure - failed communication device. Device
detected error that prevents it communicating on the
network.

Flashing
Red/Green

Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identify
Communication Faulted Request - long protocol message.

Indication

Probable Cause

I/O Status

Off

All outputs inactive

Yellow

One or more output is active and under control

Flashing Red

Open circuit detected. No load. (Off-State only)

Red

Short circuit detected. (On-State only)