Communicating with your module, Default data map for the 1734-ob2ep output module – Rockwell Automation 1734-OB2EP Point I/O Protected Output Module Installation Instructions User Manual

Page 8

Advertising
background image

8 POINT I/O Protected Output Module

Publication 1734-IN586A-EN-P - December 2001

Communicating with Your Module

I/O messages are sent to (consumed) and received from (produced)
the POINT I/O modules. These messages are mapped into the
processor’s memory. This POINT I/O output module produces 1 byte
of input data (scanner Rx) (status). It consumes 1 byte of I/O data
(scanner Tx).

Default Data Map for the 1734-OB2EP Output Module

Message size: 1 Byte

Message size: 1 Byte

7

6

5

4

3

2

1

0

Produces
(scanner Rx)

Not used

Ch1 Ch0

Channel status

Where: 0 = no error, 1 = error

7

6

5

4

3

2

1

0

Consumes
(scanner Tx)

Not used

Ch1

Ch0 Channel state

Where: 0 = Off, 1 = On