Rockwell Automation 1734-OB2EP Point I/O Protected Output Module Installation Instructions User Manual

Page 15

Advertising
background image

POINT I/O Protected Output Module 15

Publication 1734-IN586A-EN-P - December 2001

Environmental Conditions

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 55°C (-4 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bc, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating
Damp Heat):
5 to 95% non-condensing

Shock

Operating

Non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30g peak acceleration
50g peak acceleration

Vibration

IEC 60068-2-6, (Test Fc, Operating)
Tested 2g @ 10-500Hz

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to
1000MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal
ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz

Emissions

CISPR 11;
Group 1, Class A

Enclosure Type Rating

None (open-style)

Conductors Wire

Size

Category

14 AWG (2.5mm

2

) - 22 AWG (0.25mm

2

) solid or

stranded copper wire rated at 75°C or greater
3/64 inch (1.2mm) insulation maximum
2

2

Terminal Base Screw Torque

7 pound-inches (0.6Nm)

Field Wiring Terminations

0 - Output 0

1 - Output 1

2 - Output 0

3 - Output 1

4 - Common

5 - Common

6 - Supply

7 - Supply

Mass

1.15 oz/32.60 grams

Advertising