Communicate with your armorblock module – Rockwell Automation 1792-OB4E INSTL.INST ARMORBLOCK 4 OUTPUT User Manual

Page 10

Advertising
background image

ArmorBlock 4 Output Module

10

Publication 1792-5.4 – October 1996

Communicate with Your ArmorBlock Module

This ArmorBlock module acts as a slave in a master/slave environment.
It is both a “polled device” and a “change of state device.”

When configured as a polled device, a master initiates communication
by sending its polled I/O message to the ArmorBlock module. The 4
output module consumes the message, updates outputs, and returns the
status of the output bits.

When configured as a “change of state” device, productions occur
when an output fault occurs. If none has occurred within the “expected
packet rate,” a heartbeat production occurs. This heartbeat production
tells the scanner module that the ArmorBlock module is alive and ready
to communicate.

Bit

07

06

05

04

03

02

01

00

Produces

Reserved

OF3

OF2

FS1

FS0

Consumes

Reserved

O3

O2

O1

O0

Where: O = Output

OF = Output fault

Word

Bit

Description

Produces

00–03

Output fault bits – when the bit is set (1), the output is faulted. Bit
00 corresponds to output 0, bit 01 corresponds to output 1, etc.

04–07

Reserved

Consumes 00–03

Output bits – bit 00 corresponds to output 0, bit 01 corresponds to
output 1, etc.
0 = output is off; 1 = output on

04–07

Reserved